              PLC技術資料
                S7—200在變電站用交流配電盤上的應用
                發布者:用戶投稿  發布時間:2008/5/10 17:32:13
                摘  要:介紹S7—200PLC在變電站用交流配電盤上的應用。重點闡述了該系統的組成,系統功能及特點;該系統自運行以來,各項功能正常,設備運行穩定,完全達到了設計要求。 

                關鍵字:S7-200PLC, 變電站, 配電盤

                Application of S7-200 in transformer substation switchboard
                Weil in
                (Guiyang Nenghui Electric Equipment Co., Ltd, Guizhou, Guiyang)

                Abstract: This paper introduces the application of S7—200PLC in transformer substation. The paper describes configuration of hardware, function and characteristics of system. The system’s every function work well, and devices operate steadily since system run into automatic operation, so it has reached the design requirement completely.

                Key words: S7——200PLC, Transformer Substation, switchboard

                    貴陽市南供電局110kV觀水變電站是貴陽市南明區的主要供電站,變電站用配電盤運行的穩定可靠性直接影響到向整個區大部分的生產、生活供電,原用的配電盤系統功能簡單、自動化程度不高、控制方式落后,對供電局實現無人值守變電站和配網自動化帶來很多不變,也不能時刻保證城區電網供電的電源質量。因此,2005年5月對該配電盤進行了設備改造,改造以西門子公司的S7—200PLC做控制中心,TP270做監控操作中心,其它配電設備和監測設備均采用國外知名廠家產品。

                    新的配電盤通過電壓監測模塊監測1、2號變電站站用變壓器的供電情況,由PLC控制ATS開關(Automatic Transfer Switch)進行自動投切和互投操作,饋線監測模塊將饋線裝置的狀態、動作及多種電能參數進行監控,確保變電站的各輔助系統穩定運行,所有裝置的操作、運行情況和電能參數通過PLC在TP270上得以體現和記錄,并通過RS-485或LAN將各種信號傳送到供電調度中心和集控中心,以便及時進行供電調度和設備檢修。

                    設備改造中使用了西門子公司的224XP-CPU、TP270人機界面、EM221數字量輸入模塊、EM222數字量輸出模塊和CP243-1以太網通訊模塊。


                圖1 企業照片


                圖2系統結構圖

                名 稱
                型 號
                數 量
                備 注
                PLC
                224XP
                1
                AC/DC/R/Port×2
                DI
                EM221×8
                4
                DC24V
                DO
                EM222×8
                2
                DC24V
                CP
                243-1
                1
                HMI
                TP270
                1
                10寸
                電壓監測模塊
                GKR-02
                2
                多功能監測模塊
                DIRIS AP
                1
                饋線開關狀態監測模塊
                OF
                40
                DC24V
                隔離開關
                CD630A
                2
                ATS
                MICRO
                1
                電動操作饋電開關
                NS200A
                2
                饋電開關
                NS125A
                6
                饋電開關
                C65/63A
                28
                電源模塊
                24V/2.5A
                1
                編程軟件
                MicroWin4.0
                1
                編程軟件
                ProTools/Pro6.0
                1

                表1 系統配置表

                [NextPage]


                圖3應用中的畫面

                    應用S7-200PLC升級過后的變電站站用配電盤(智能配電屏),改變了以前電能數據采集麻煩、運行方式單一、必須現場手動操作等問題,現在除了保留必須的手動操作方式外,根據運行方式PLC能控制ATS開關任意切換在電源I或II上運行,當運行電源進線失壓時,另一電源進線能可靠自投或恢復,同時可進行遠程操作,解決了目前ATS產品控制投切不準確,操作方式單一和遠程控制的問題。改造以前的配電盤上有著各種電能儀表,現在只需一塊多功能儀表就能完成電壓、電流、頻率、有功功率、無功功率等各種電能參數的監測、采集和數據分析,還有諧波分析、模擬量和報警輸出等功能。站用配電屏還能監控每一饋電回路的電流和工作狀態,整個配電盤的任何一個動作、操作和故障報警都及時顯示并儲存在TP270上,通過MODBUS總線可以把這些數據傳到附近的控制中心,也可以通過以太網將數據傳到數公里之外的調度中心,以便于進行更好的運行維護和管理。

                    在設計過程中最大的問題就是如何將智能儀表的數據通過S7-200PLC讀到TP270上。本系統中的智能儀表用的是MODBUS_RUT協議,只能做從站使用,也就是說S7-200PLC必須做主站去讀取儀表的數據,在現行的資料中只有S7——200PLC做MODBUS從站的資料,要S7-200PLC做主站就只有自己編寫用自由口做MODBUS主站的程序,由于儀表提供的數據較多且數據地址分散,再加上要求每秒刷新一次,還要做數據的CRC校驗,編寫這樣的通訊程序是有一定難度的,如果逐一地址的編寫程序,那么程序就會過長,會影響總循環時間,不但做不到1秒鐘刷新一次,可能還會引起端口發送、接收沖突和CRC校驗出錯,經過反復的研究實驗,最后在程序中采用了用計數器來輪詢地址的方法,從而減少了程序量和總循環時間。部分程序如下:(OB1主要功能為初始化端口為自由口,初始化發送和接收的數據格式,設定輪詢時間,輪詢和中斷連接;SBR5和SBR6做發送和接收數據的CRC校驗,CRC檢驗主要通過字節異或循環,移位循環和公式異或做發送數據的CRC校驗;中斷1為接收數據;中斷2對接收CRC校驗結果驗證)

                OB1
                LD     SM0.1                       初始化端口
                MOVB   16#09, SMB30
                MOVB   16#9C, SMB87
                MOVW   +150, SMW92
                MOVW   +0, SMW90
                MOVB   50, SMB94

                [NextPage]
                LD     SM0.1                     初始化發送數據
                MOVB   16#08, VB2100
                MOVB   16#05, VB2101
                MOVB   16#03, VB2102
                MOVB   16#03, VB2103
                MOVB   16#0, VB2104                                                      
                MOVB   16#0, VB2105
                MOVB   16#02, VB2106
                LD     SM0.1                   初始化接收數據
                MOVB   16#09, VB1200
                MOVB   16#05, VB1201
                MOVB   16#03, VB1202
                MOVB   16#04, VB1203
                LD     SM0.0                     設定輪詢時間
                AN     T96
                TON    T32, +150
                LD     SM0.0
                A      T32
                TON    T96, +150
                LD     T32
                EU
                LD     C1
                CTU    C1, 16#10
                LD     SM0.0
                AW=    16#0, C1
                EU
                MOVW   16#0300, VW2103            發送輪詢數據
                CALL   CRC:SBR5
                XMT    VB2100, 0
                LD     SM0.0
                AW=    16#1, C1
                EU
                MOVW   16#0302, VW2103
                CALL   CRC:SBR5
                XMT    VB2100, 0
                LD     SM0.0
                AW=    16#02, C1
                EU
                MOVW   16#0304, VW2103
                CALL   CRC:SBR5
                XMT    VB2100, 0
                …… ……
                LD     SM0.7                      中斷連接
                ATCH   INT_0:INT0, 9
                ATCH   INT_1:INT1, 23
                ENI
                SRB6(SBR5同SBR6)
                LD     Always_On:SM0.0       讀出數據長度 ,初始化CRC字
                MOVB   VB1200, VB1301
                MOVW   VW1300, VW1302
                -I     16#02, VW1302
                MOVW   16#FFFF, VW1306
                MOVD   &VB1200, VD1400
                FOR    VW1304, 16#1, VW1302
                LD     Always_On:SM0.0           字節異或循環
                +D     16#1, VD1400
                MOVB   *VD1400, VB1410
                XORB   VB1410, VB1307
                FOR    VW1310, 16#1, 16#08
                LD     Always_On:SM0.0           移位循環
                MOVW   VW1306, VW1420
                SRW    VW1306, 1
                LD     SM1.1                     公式異或
                XORW   16#A001, VW1306
                NEXT
                NEXT
                LD     Always_On:SM0.0          CRC16字傳遞
                MOVB   VB1307, VB1100
                MOVB   VB1306, VB1101
                INT1
                LD     Always_On:SM0.0
                RCV    VB2200, 0
                INT2
                LD     SM86.7
                O      SM86.6
                O      SM86.0
                CRETI
                LD     Always_On:SM0.0
                MOVD   VD2204, VD1204
                LD     Always_On:SM0.0
                CALL   CRC16:SBR6
                LDW<>  VW1100, VW2208
                CRETI
                LDW=   16#0, C1
                MOVD   VD2204, VD2500
                LDW=   16#1, C1
                MOVD   VD2204, VD2504
                …… ……
                    經過改造的設備自2005年7月運行以來,系統穩定、功能強大、操作簡單,贏得了用戶的一致好評,為變電站的無人值守和變電站的安全運行提供了有利保障。

                版權聲明PLC信息網轉載作品均注明出處,本網未注明出處和轉載的,是出于傳遞更多信息之目的,并不意味 著贊同其觀點或證實其內容的真實性。如轉載作品侵犯作者署名權,或有其他諸如版權、肖像權、知識產權等方面的傷害,并非本網故意為之,在接到相關權利人通知后將立即加以更正。聯系電話:0571-87774297。